MODEL |
RTS-LI-2k0-3U-LCD-3×9 |
Power rating (seeming/active) |
2kVA/1800W |
Input |
Input voltage |
230Vac |
Scope of the input voltage |
Full validity (230Vac) ± 26% , 45-55Hz ± 0,5%Hz |
Power factor |
≥ 0,9 |
Output |
Output voltage |
220V/230V/240VAC ± 265 available placing through LCD – battery operated mode
220V/230V/240VAC ± 265 available placing through LCD – network
|
Frequency of the output voltage |
Synchronized under the network procedure, 50/60Hz ± 0,2Hz in the battery operated mode |
Shape of the output voltage |
Clean sine |
Harmonic distortions |
≤ 5% (linear burden), |
Time of switching for UPS |
From the AC mode to battery operated: 8ms |
Output sockets |
6x IEC C13 |
Efficiency |
Network mode/AC |
≤ 98% |
Battery mode |
≤ 85% (linear burden) |
Battery |
Permanent tension |
36V |
Configuration |
3x12V/9Ah |
Charging current (standart) |
1A |
Charging current (option) |
1-5A (standart1A) |
Time of supporting (min. )100%/75%/50% |
2 min / 4min / 7min |
Time of loading |
8 hours for 90% capacities |
Additional battery packgage (option)
|
KU-BAT-2URT-3×9-36 (max 4szt),
KU-BAT-2URT-6×9-24 (max 2szt),
|
Alerts |
Rock bottom of the battery |
The short signal as the second on time 0.16 sek and 0.16 sek breaks |
Overload |
Long signal about time 2 sek and 0.5 sek breaks |
Battery mode |
Short sound as 5 seconds, put out after 60 sek |
Environmental parameters |
Relative humidity in working hours |
20~90% RH @ 0~40°C (noncondensing) |
Level of noise |
≤ 5 dB (1m) |
Communication |
In the USB standard |
Support for Windows®98/2000/2003/XP/Vista/2008/Windows®7/Windows®8 |
SNMP (opcja) |
Ordering the SNMP manager from the level and web browsers |
Styki bezpotencjałowe (opcja) |
Possibility of adding the card |
Dismesions and weight |
Weight net/gross(kg) |
21,3/24,5 |
Dismesions L./W./H. (mm) w/l(d)/h |
440×410(430)x132 |
Dimensions of the package L./W./H. (mm) |
505x611x235 |
Norms |
Low-voltage directive |
EN62040-1:2008+A1:2013 |
Electromagnetic compatibility |
EN62040-2:2006
EN61000-3-2:2014 Class A
|